Technical Data
10-2
7SA522 Manual
C53000-G1176-C119-2
10.1
General Device Data
10.1.1 Analog Inputs
Nominal frequency
f
N
50 Hz or 60 Hz(adjustable)
Current Inputs
Nominal current
I
N
1 A or 5 A
Power consumption per phase and earth path
– at I
N
= 1 A
approx. 0.05 VA
– at I
N
= 5 A
approx. 0.3 VA
– Sensitive earth fault detection at 1 A
approx. 0.05 VA
Current overload capability per input
– thermal (rms)
500 A for 1 s
150 A for 10 s
20 A continuous
– dynamic (pulse)
1250 A (half cycle)
Current overload capability for sensitive earth current input
– thermal (rms)
300 A for 1 s
100 A for 10 s
15 A continuous
– dynamic (pulse)
750 A (half cycle)
Voltage Inputs
Nominal voltage
U
N
80 V to 125 V (adjustable)
Power consumption per phase at 100 V
≤
0.1 VA
Current overload capability per phase
– thermal (rms)
170 V continuous
10.1.2 Power Supply
Direct Voltage
Voltage supply via integrated DC/DC converter:
Permissible AC Ripple Voltage,
peak to peak
≤
15 % of the nominal power supply voltage
Power consumption
– quiescent
approx. 5 W
– energized with 7SA522*–*A/E/J
approx. 12 W
with 7SA522*–*C/G/L
approx. 15 W
with 7SA522*–*D/H/M
approx. 18 W
Nominal power supply direct voltage U
NDC
24/48 VDC
60/110/125 VDC
Permissible voltage ranges
19 to 58 VDC
48 to 150 VDC
Nominal power supply direct voltage U
NDC
110/125/220/250 VDC
220/250 VDC
Permissible voltage ranges
88 to 300 VDC
176 to 300 VDC
Summary of Contents for siprotec 7SA522
Page 20: ...7SA522 Manual C53000 G1176 C119 2 ...
Page 64: ...7SA522 Manual C53000 G1176 C119 2 ...
Page 89: ...SIPROTEC 4 Devices 4 25 7SA522 Manual C53000 G1176 C119 2 Figure 4 20 CFC Logic example ...
Page 408: ...7SA522 Manual C53000 G1176 C119 2 ...
Page 456: ...7SA522 Manual C53000 G1176 C119 2 ...
Page 516: ...7SA522 Manual C53000 G1176 C119 2 ...
Page 620: ...Appendix B 48 ...