Functions
6-219
7SA522 Manual
C53000-G1176-C119-2
Broken Conductor
A broken conductor of the protected line or in the current transformer secondary circuit
can be detected, if the minimum current
flows via the feeder. If a
current symmetrie failure is detected and the minimum current is below the threshold
(address 1130, refer to subsection 6.1.3), an interruption of this
conductor may be assumed. After approximately 5 s the device issues the alarm
“
)DLO&RQGXFWRU
”.
Voltage Symmetry
During normal system operation, a certain degree of voltage symmetry can be as-
sumed. The symmetry is monitored in the device with a magnitude comparison. The
smallest phase voltage is compared to the largest. Non-symmetry is detected when
|U
min
| / |U
max
|
<
as long as
|Umax|
>
U
max
is the largest and U
min
is the smallest of the three voltages. The symmetry factor
provides a measure of the voltage unsymmetry, the threshold value
defines the lower limit of the operating range for this monitoring
function (refer to Figure 6-116). Both parameters can be set. The reset ratio is approx.
97 %.
This failure is alarmed by “
)DLO8EDODQFH
”.
Figure 6-116 Voltage symmetry monitoring
Voltage Phase
Rotation
The verification of the faulted phases and the phase preference, direction measure-
ment and polarization with quadrature voltages usually demand clockwise rotation of
the measured values. The phase rotation of the measured voltages is checked by
monitoring of the voltage phase sequence.
U
L1
before U
L2
before U
L3
This check takes place if each measured voltage has a minimum magnitude of
|U
L1
|, |U
L2
|, |U
L3
| > 40 V/
√
3
In the event of negative phase rotation, the alarm “
” is issued.
If the system has a negative phase rotation, this must have been set during the con-
figuration of the power system data (Sub-section 6.1.1). In such event, the phase ro-
tation monitoring applies to the corresponding opposite phase sequence.
U
min
V
%$/$1&(8/,0,7
slope:
%$/)$&7258
U
max
V
Summary of Contents for siprotec 7SA522
Page 20: ...7SA522 Manual C53000 G1176 C119 2 ...
Page 64: ...7SA522 Manual C53000 G1176 C119 2 ...
Page 89: ...SIPROTEC 4 Devices 4 25 7SA522 Manual C53000 G1176 C119 2 Figure 4 20 CFC Logic example ...
Page 408: ...7SA522 Manual C53000 G1176 C119 2 ...
Page 456: ...7SA522 Manual C53000 G1176 C119 2 ...
Page 516: ...7SA522 Manual C53000 G1176 C119 2 ...
Page 620: ...Appendix B 48 ...