Functions
6-192
7SA522 Manual
C53000-G1176-C119-2
Displacement
Voltage
Figure 6-95 shows the logic diagram of the displacement voltage stage. The funda-
mental frequency voltage is filtered out of the measured voltage, so that higher har-
monics and transient voltage peaks are largely suppresses. If the set phase voltage
is exceeded, this is alarmed. After expiry of the settable time delay
trip command is issued. The reset ratio of this stage can be set with the parameter
.
For this stage, the trip command can be transmitted to the other line end or to any oth-
er item of plant as well. The impulse output “
8R6(1'
”, the duration of which can be
set with the parameter
is used for this purpose.
If the measured voltage supervision “Fuse–Failure–Monitor” has picked up, the dis-
placement voltage protection is automatically blocked.
Figure 6-95 Logic diagram of the zero sequence voltage over voltage protection
Any Single Phase
Voltage
As the function of the displacement voltage stage is separated from the phase voltage
stage it may also be used for any other single-phase voltage, provided that the fourth
voltage measurement input U
4
of the device has been allocated accordingly (refer also
to Section 6.1.1 under “Voltage Transformer Connection”).
6.13.2 Applying the Function Parameter Settings
The overvoltage protection can only operate if it was selected to be
(QDEOHG
during
the configuration of the scope of functions in the device (refer to Section 5.1, address
).
Phase Voltage
Stage
The phase voltage stage can be switched
21
or
2))
under address
. Further-
more, the stage can be set to
$ODUP2QO\
; i.e. the stage is in service and also issues
alarms, but does not generate any trip commands. The impulse output is however not
suppressed.
The settings for the voltage measurement and the timers depends on the application.
If steady-state overvoltages on long unloaded lines must be detected, the
stage (address
) is set at least 10 % above the maximum operational steady-
state phase-earth voltage that may arise (the tolerance and reset ratio must be taken
into account). The time delay
(address
) should be set to several sec-
onds in this case to avoid tripping due to transient overvoltages.
If large overvoltages with short duration must be detected, a larger pick-up threshold
(address
) must be set, e.g. 1
1
/
2
–times the nominal phase-earth volt-
age. For the time delay
(address
) a setting of 0,1 s to 0,2 s should be
sufficient in this case.
8!
3U0>
T
0
T
78
76HQ,PS8R
85HVHW5DWLR
U
L1-E
+U
L2-E
+U
L3-E
4350 3Uo PICKUP
4362 3Uo TRIP
4351 3Uo SEND
Summary of Contents for siprotec 7SA522
Page 20: ...7SA522 Manual C53000 G1176 C119 2 ...
Page 64: ...7SA522 Manual C53000 G1176 C119 2 ...
Page 89: ...SIPROTEC 4 Devices 4 25 7SA522 Manual C53000 G1176 C119 2 Figure 4 20 CFC Logic example ...
Page 408: ...7SA522 Manual C53000 G1176 C119 2 ...
Page 456: ...7SA522 Manual C53000 G1176 C119 2 ...
Page 516: ...7SA522 Manual C53000 G1176 C119 2 ...
Page 620: ...Appendix B 48 ...