$SSHQGL[
5:
9
&*&
©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©
20 df/dt PROT. - RATE-OF-FREQUENCY-CHANGE PROTECTION
20 df/dt
State of the rate-of-frequency-change prot.
OFF
[ ] off
ON
[ ] on
20 df1
Pick-up value of the df1/dt stage
min. 1.0
Hz/s
max. 10.0/Ñ
©©©©
20 T df1
Time delay for trip df1/dt
min. 0.00
s
max. 20.00/Ñ ©©©©
20 df1&f
State of AND-combination with fault f1
OFF
[ ] off
ON
[ ] on
20 df2
Pick-up value of the df2/dt stage
min. 1.0
Hz/s
max. 10.0/Ñ
©©©©
20 T df2
Time delay for trip df2/dt
min. 0.00
s
max. 20.00/Ñ ©©©©
20 df2&f
State of AND-combination with fault f2
OFF
[ ] off
ON
[ ] on
20 df3
Pick-up value of the df3/dt stage
min. 1.0
Hz/s
max. 10.0/Ñ
©©©©
20 T df3
Time delay for trip df3/dt
min. 0.00
s
max. 20.00/Ñ ©©©©
20 df3&f
State of AND-combination with fault f3
OFF
[ ] off
ON
[ ] on
20 df4
Pick-up value of the df4/dt stage
min. 1.0
Hz/s
max. 10.0/Ñ
©©©©
20 T df4
Time delay for trip df4/dt
min. 0.00
s
max. 20.00/Ñ ©©©©
20 df4&f
State of AND-combination with fault f4
OFF
[ ] off
ON
[ ] on
20 BL U<
Min. volatge for rate-of-freq.-change prot.
min. 20
V
max. 100/Ñ
©©©©
©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©©