2.9 Process bus link
87
6MD665 Manual
C53000-G1876-C103-3
2.9
Process bus link
The Bay Processing Unit 6MD665 allows direct communication with SICAM HV mod-
ules. The process bus interface is equipped with an Ethernet module.
2.9.1
Description
General
Upon delivery of the device, there are no process information or allocations present.
The information is entered by importing data from
• the parameterisation tool for SICAM HV modules ModPara and
• from the information catalogue of the parameterisation tool DIGSI
®
Between the two parameterisation tools, carry out an export of the parameterised
information from ModPara to DIGSI
®
so that the process information of the submod-
ules SICAM HV can be converted into process objects of the SIPROTEC
®
4 device
6MD665.
For a file transfer, the Process Communication Unit (PCU) submodule structure is to
be illustrated in a two-level directory tree in the parameter set of the SIPROTEC
®
4
device 6MD665. In addition, data must be made available to the PCUs via the
process bus (communication addresses).
The parameterisation sequence is set as follows:
• ModPara (parameterise SICAM HV module)
• DIGSI
®
(parameterise SIPROTEC
®
4 device 6MD665)
• ModPara (parameterise communication module)
The following figure shows the physical structure of a system.
Summary of Contents for SIPROTEC 6MD665
Page 8: ...Preface vi 6MD665 Manual C53000 G1876 C103 3 ...
Page 14: ...Contents vi 6MD665 Manual C53000 G1876 C103 3 ...
Page 140: ...3 Installation and Commissioning 126 6MD665 Manual C53000 G1876 C103 3 ...
Page 166: ...4 Technical Data 152 6MD665 Manual C53000 G1876 C103 3 ...
Page 210: ...Literature 196 6MD665 Manual C53000 G1876 C103 3 ...
Page 222: ...Index 208 6MD665 Manual C53000 G1876 C103 3 ...