General Device Data
Analog Inputs
GIS Low-Power Current Input (via Module IO240)
All current, voltage, and power data are specified as RMS values.
Rated frequency f
rated
50 Hz
60 Hz
Rated current I
rated
- 50 Hz
Min. 13 mV
Max. 332 mV
Rated current I
rated
- 60 Hz
Min. 15.4 mV
Max. 386 mV
Measuring range
50 ⋅ I
rated
(Protection channel)
1.6 ⋅ I
rated
(Metering channel)
Power consumption per current
circuit at rated current
Max. 40 mVA
Burden = 9.5 kΩ
Thermal rating
Max. input voltage = 20 V
Accuracy
Class 5TPE (Protection channel)
Class 0.2S (Metering channel)
Voltage Input
All current, voltage, and power data are specified as RMS values.
Rated frequency f
rated
50 Hz, 60 Hz
16.7 Hz (for rail devices only)
Input and output modules
IO102, IO202, IO208, IO211,
IO214
IO215
Measuring range
0 V to 200 V
0 V to 7.07 V
Burden
< 0.1 VA
< 0.01 VA
Thermal rating
230 V continuously
20 V continuously
GIS Low-Power Voltage Input (via Module IO240)
All current, voltage, and power data are specified as RMS values.
Rated frequency f
rated
50 Hz
60 Hz
Rated voltage V
rated
- 50 Hz
Min. 0.25 mA
Max. 2.00 mA
Rated voltage V
rated
- 60 Hz
Min. 0.30 mA
Max. 2.20 mA
Measuring range
2 ⋅ V
rated
Power consumption per current
circuit at rated current
Max. 1 mVA
Burden = 50 Ω
Thermal rating
Max. input current = 4.4 mA
Accuracy
Class 0.1
Measuring-Transducer Inputs (via Module ANAI-CA-4EL)
Insulation class
SELV (Safety Extra Low Voltage) (according to IEC 60255-27)
Connector type
8-pin terminal spring
12.1
12.1.1
Technical Data
12.1 General Device Data
SIPROTEC 5, Merging Unit 6MU85, Manual
787
C53000-G5040-C074-1, Edition 01.2020