Addr.
Parameter
Setting Options
Default Setting
Comments
8202
Alarm Delay
1 .. 30 sec
2 sec
Delay Time for alarm
Information List
No.
Information
Type of
Informa-
tion
Comments
6851
>BLOCK 74TC
SP
>BLOCK 74TC
6852
>74TC trip rel.
SP
>74TC Trip circuit superv.: trip relay
6853
>74TC brk rel.
SP
>74TC Trip circuit superv.: brk relay
6861
74TC OFF
OUT
74TC Trip circuit supervision OFF
6862
74TC BLOCKED
OUT
74TC Trip circuit supervision is BLOCKED
6863
74TC ACTIVE
OUT
74TC Trip circuit supervision is ACTIVE
6864
74TC ProgFail
OUT
74TC blocked. Bin. input is not set
6865
74TC Trip cir.
OUT
74TC Failure Trip Circuit
Malfunction Responses of the Monitoring Functions
In the following malfunction responses of monitoring equipment are clearly listed.
Description
Malfunction Responses
Depending on the type of malfunction discovered, an annunciation is sent, a restart of the processor system is
initiated, or the device is taken out of service. After three unsuccessful restart attempts, the device is taken out
of service. The operational readiness NC contact operates to indicate the device is malfunctioning. Also, the
red LED ”ERROR" lights up on the front cover, if the internal auxiliary voltage is present, and the green ”RUN"
LED goes out. If the internal auxiliary voltage fails, all LEDs are dark.
provides a summary of the
monitoring functions and the malfunction responses of the relay.
Table 2-14
Summary of malfunction responses by the protection relay
Monitoring
Possible Causes
Malfunction
Response
Message (No.)
Output
AC/DC supply voltage loss
External
(Nominal voltage)
internal (power
supply)
Device shutdown
All LEDs dark
DOK
2)
drops
out
Internal supply voltages
Internal (power
supply)
Device shutdown
LED "ERROR"
DOK
2)
drops
out
Buffer battery
Internal (buffer
battery)
Message
Fail Battery
(177)
Hardware watchdog
Internal
(processor failure)
Device shutdown
1)
LED "ERROR"
DOK
2)
drops
out
Software watchdog
Internal
(processor failure)
Restart attempt
1)
LED "ERROR"
DOK
2)
drops
out
Working memory ROM
Internal (hardware)
Relay aborts restart,
device shutdown
LED blinkt
DOK
2)
drops
out
2.12.2.4
2.12.3
2.12.3.1
Functions
2.12 Monitoring Functions
SIPROTEC 4, 7SJ62/64, Manual
197
C53000-G1140-C207-8, Edition 08.2016
Summary of Contents for SIPROTEC 4
Page 8: ...8 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 18: ...18 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 30: ...30 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 540: ...540 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 594: ...594 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 720: ...720 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...