Addr.
Parameter
C
Setting Options
Default Setting
Comments
5522
U> Reclose
10.00 .. 210.00 V
95.00 V
Voltage threshold for reclo-
sure rel.
5523
T Reclose
0.00 .. 3600.00 sec
0.00 sec
Reclosure Delay Time
5524
Pos. f-diff
0.01 .. 5.00 Hz
0.05 Hz
Pos. f-diff threshold for
reclosure rel.
5525
Neg. f-diff
-5.00 .. -0.01 Hz
-2.50 Hz
Neg. f-diff threshold for
reclosure rel.
5526A
Incl. 27/Q Trip
NO
YES
NO
Include 27/Q Trip for reclo-
sure rel.
Information List
No.
Information
Type of
Informa-
tion
Comments
6401
>27/Q Block
SP
>QV-Protection Blocked
6411
27/Q OFF
OUT
27/Q -Protection off
6412
27/Q block
OUT
27/Q -Protection blocked
6413
27/Q ACT
OUT
27/Q -Protection active
6421
27/Q Gen TRIP
OUT
27/Q -Protection Gen TRIP
6422
27/Q Grid TRIP
OUT
27/Q -Protection Grid TRIP
6423
27/Q PICKUP
OUT
27/Q-Protection PICKUP
6424
Reclosure rel.
OUT
Reclosure release
6425
27/Q blk.b.Inr.
OUT
27/Q pickup blocked by Inrush
2.10.4
Functions
2.10 27/Q
SIPROTEC 4, 7SJ62/64, Manual
171
C53000-G1140-C207-8, Edition 08.2016
Summary of Contents for SIPROTEC 4
Page 8: ...8 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 18: ...18 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 30: ...30 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 540: ...540 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 594: ...594 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 720: ...720 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...