[lo-crossblk-fkt-1ende-110428, 1, en_US]
Figure 2-33
Logic diagram of the cross-block function for one end
Setting Notes
The inrush current detection is required for the following applications:
•
For the differential protection if an inductance is located in the protected zone.
•
For the time overcurrent protection if the protected line ends on a transformer.
Inrush current detection can be turned
ON
or
OFF
at address 2301
INRUSH REST.
.
It is based on the evaluation of the second harmonic which exists in the inrush current. Ex-works a ratio of
15 % of the
2nd HARMONIC
Ι
2fN
/
Ι
fN
is set under address 2302, which can normally be taken over. However,
the component required for restraint can be parameterized. In order to be able to achieve a higher degree of
restraint in case of exceptionally unfavorable inrush conditions, you may also set a smaller value.
However, if the local measured current exceeds a value set in address 2305
MAX INRUSH PEAK
, there will be
no inrush restraint. The peak value is decisive. The set value should be higher than the maximum inrush
current peak value that can be expected. For transformers set the value above √2·
Ι
NTransf
/u
kTransf
. If a line ends
on a transformer, a smaller value may be selected, considering the damping of the current by the line impe-
dance.
The crossblock function can be activated (
YES
or deactivated (
NO
) in address 2303
CROSS BLOCK
. The time
after exceeding of the current threshold for which this crossblock is to be activated is set under address 2310
CROSSB 2HM
. With the setting ∞ the crossblock function is always active until the second harmonic content in
all phases has dropped below the set value.
Settings
Addr.
Parameter
Setting Options
Default Setting
Comments
2301
INRUSH REST.
OFF
ON
OFF
Inrush Restraint
2302
2nd HARMONIC
10 .. 45 %
15 %
2nd. harmonic in % of funda-
mental
2303
CROSS BLOCK
NO
YES
NO
Cross Block
2305
MAX INRUSH PEAK
5.5 .. 125.0 A
75.0 A
Maximum inrush-peak value
2310
CROSSB 2HM
0.00 .. 60.00 sec
0.00 sec
Time for Crossblock with 2nd
harmonic
2.5.2
2.5.3
Functions
2.5 InRush Restraint
92
SIPROTEC 4, 7SD80, Manual
E50417-G1100-C474-A2, Edition 02.2018
Summary of Contents for SIPROTEC 4 7SD80
Page 8: ...8 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 10: ...10 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 18: ...18 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 248: ...248 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 298: ...298 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 312: ...312 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 322: ...322 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 400: ...400 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 402: ...402 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...