SIPLUS PSU (6DL3500-8BA)
SIPLUS PSU Power Supply Unit
A5E00854207E
17 of 30
Copyright (C) Siemens AG 2018
V 8.00 released
2018-05-03
5.4 Supply Outputs
Max. permitted constant current
6
Imax = 15 A
Voltage drop from feeder terminal up to sup-
ply terminals X1-X20
typ. 1.00 V, max. 1.30 V
fuse link
type
Tripping characteristic
7
Rated voltage
blade fuse according to DIN 72581-3
(withdrawn standard) style C
15 A slow acting (5-fold rated current 200 ms min.)
≥ 45 V
Line terminal connection
plug connectors, 2-pole
COMBICON MSTB 2,5 HC/ 2-ST-5.08 RDB
min. wire cross-section 0.25 mm
2
or AWG 24
max. wire cross-section 2.5 mm
2
or AWG 12
(see chapter 9 “Order Designations”)
NOTICE
Possible damages of the facility!
At insufficient dimensioning of the wire cross-section the respective line may
be excessive charged. This leads to strong heating of the conductor up to
damage.
The wire cross-section has to be dimensioned according to the nominal current
of the selected fuse and the expected load current.
Figure 8: Supply outputs
6
When using fuse-links of the type Little fuse TF90 – 15 A (delivery condition) and considering the maximum
permitted continuous current at the input terminals, see chapter 5.3. For selection of the correct fuses see chap-
ter 9 “Order Designations”.
7
For selectivity when connecting a FUM-Sub rack EU 902 / EU903 / EU905 or a S7-400H Sub rack