background image

SIPLUS CMS2000 VIB-MUX  6AT8002-2AA00 

 A5E31647341/004, 03/2016 

3

 

Installation 
Standard rail mounting and removable terminals 

(see Figure 2)  

Mandatory sequence of expansion modules when 

expanding the SIPLUS CMS2000 system:  

[Basic Unit VIB] + [VIB-MUX 1/2] + [temperature 

module 1/2] 
Connecting 

Connect the stripped cable ends to the relevant

connecting terminals and tighten the terminals (see

Figure 2 and Figure 3).

Connecting system interfaces (front): Connect the

connecting cable between the Basic Unit VIB and VIB-

MUX.

Terminal assignment 

Terminal block A 
2P24 

Power supply for the process 

functionality. The process supply and 

logic supply are galvanically isolated 

internally. 

2M24 

NC 

Not connected 

VIB7+ 

IEPE sensor input 7 

NC 

Not connected 

VIB8+ 

IEPE sensor input 8 

Terminal block B 
VIB A+ 

IEPE output A+ for connection to an 

IEPE input on the Basic Unit VIB 

(terminal block B VIB1+ or terminal block 

A VIB2+) 

FE 

Functional grounding 

VIB A- 

IEPE output A- for connection to an 

IEPE input on the Basic Unit VIB 

(terminal block B VIB1- or terminal block 

A VIB2-) 

VIB 7- 

IEPE sensor input 7 

NC 

Not connected 

VIB8- 

IEPE sensor input 8 

Terminal block C 
VIB1- ... VIB6-  IEPE sensor inputs 1 to 6 

Terminal block D 
VIB1+ ... VIB6+  IEPE sensor inputs 1 to 6 

Technical specifications 

Interfaces 
Logic power supply (supplied from system interface) 
Voltage 

5 V DC (±5 %) 

Current consumption  < 10 mA 
Power loss (typical) 

< 50 mW 

Process power supply (supplied from external 24 V 

supply) 

Interfaces 
Voltage 

24 V DC (±20%) 

Current consumption 

(nominal) 

< 100 mA 

Power consumption 

< 2.4 W 

Sensor inputs (IEPE sensors) 
Infeed current 

(typical) 

4 mA 

Input voltage, useful 

signal 

±1 V (2 Vpp) 

System interface 
Connectable modules 

Temperature module

(3UF7700-1AA00-0)

VIB-MUX (6AT8002-2AA00)

Maximum 

configuration 

Basic Unit VIB + 2 VIB-MUX + 2 

temperature modules 

Ambient conditions 
Ambient temperature in 

operation 

-20 °C to +65 °C 

Ambient temperature 

during storage and 

transport 

-25 °C to +85 °C 

Relative operating 

humidity 

< 95% (no condensation) 

Maximum height above 

sea level 

1500 m 

Degree of protection 

IP20 

General technical specifications 
Dimensions (W x H x D) 

45 mm x 106 mm x 124 mm 

Weight 

270 g 

Mounting 

Mounting onto standard DIN 

rail according to EN 

60715TH35-15 

Approvals 
CE, C-Tick 

EMC Directive 2004/108/EEC 

UL 

UL 508, CSA C22.2 No. 142 

Technical Assistance 
Telephone: +49 (0) 911-895-7222 (8°° - 17°° CET) 

email (

mailto:[email protected]

 

Internet (

Http://www.siemens.com/automation/support-

request

 

Additional documentation 
The SIPLUS CMS2000 Operating Instructions can also be 

found on the Internet 

(

http://support.automation.siemens.com/WW/view/en/56901

901

). 

Additional information 
Additional information on SIPLUS CMS can be found on the 

Internet (

http://www.siemens.de/siplus-cms

). 

Reviews: