Troubleshooting Procedures
3.12 High Vibration
PS2 Troubleshooting Guide
Service Manual, 03/2017, A5E36661550-AA
27
3.12
High Vibration
Too much vibration can cause erroneous feedback and damage positioner. The SIPART
PS2 vibration specifications are:
●
Harmonic oscillations (sine-wave) according to EN 60068-2-6/10.2008
–
3.5 mm (0.14"), 2 ... 27 Hz, 3 cycles/axis, 98.1 m/s² (321.84 ft/s²), 27 ... 300 Hz, 3
cycles/axis
●
Bumping (half-sine) according to EN 60068-2-27/02.2010
–
150 m/s² (492 ft/s²), 6 ms, 1000 shocks/axis
●
Noise (digitally controlled) according to EN 60068-2-64/04.2009
–
10 ... 200 Hz; 1 (m/s²)²/Hz (3.28 (ft/s²)²/Hz)
–
200 ... 500 Hz; 0.3 (m/s²)²/Hz (0.98 (ft/s²)²/Hz)4 hours/axis
●
Recommended continuous duty range of the complete fitting
–
<= 30 m/s² (98.4 ft/s²) without resonance sharpness
●
If excessive vibration cannot be avoided, consider Non-Contacting technology. Contact
Siemens technical support for assistance: 1-800-333-7421.
3.13
Initialization Incomplete
Fault Profile (symptoms) Possible Cause(s)
Corrective Measures
Positioner remains in
"RUN 1"
•
Waiting time of 1 minute not ac-
complished.
•
Loose or Worn Linkage (Page 29)
•
Supply air not connected or Insuffi-
cient Supply Air (Page 28)
•
Valve Block Failure (Page 38)
•
A waiting time of 2 minutes
is essential. Start initializa-
tion from a mid-stroke posi-
tion.
•
(Page 29)
•
(Page 28)
Positioner remains in
"RUN 2"
•
Transmission ratio selector and
parameter "2. YAGL" not set cor-
rectly and/or real stroke does not
match.
•
Incorrectly set stroke on the lever.
•
Valve Block issue, see Valve Block
•
(Page 50)
•
See "Possible Messages"
table of Leaflet.
•
If "Tolerance Band Down
Violated" message, adjust
slip-clutch as instructed in
leaflets