9.7.3
Ambient temperature
Maximum permitted ambient temperature during operation in hazardous areas with potentially
explosive atmosphere
Positioner
Temperature class T4
6DR710* and 6DR711*
-20°C ≤ Ta ≤ +80°C
9.7.4
Electrical specifications
Basic electronics with explosion protection
Ex "ia"
Ex "ic"
Ex "ec", "tb"
Analog input (AI) HART / 4 … 20 mA
Terminals 6(+) and 7(-)
For connecting to circuits with the following
peak values
U
i
≤ 30 V
U
i
≤ 30 V
U
n
≤ 30 V
I
i
≤ 100 mA
I
i
≤ 100 mA
I
n
≤ 100 mA
P
i
≤ 750 mW
-
-
C
i
≤ 6 nF
C
i
≤ 6 nF
-
L
i
≤ 221 μH
L
i
≤ 221 μH
-
Analog output (AO) 4 … 20 mA
Terminals 61(+) and 62(-)
For connecting to circuits with the following
peak values
U
i
≤ 30 V
U
i
≤ 30 V
U
n
≤ 30 V
I
i
≤ 100 mA
I
i
≤ 100 mA
I
n
≤ 100 mA
P
i
≤ 750 mW
-
-
C
i
≤ 7 nF
C
i
≤ 7 nF
-
L
i
≤ 66 μH
L
i
≤ 66 μH
-
Analog output (AO) galvanically isolated from
the analog input (AI)
Test voltage
840 V DC, 1 s
9.8
Mobile IQ app and AW050 Bluetooth adapter
9.8.1
SITRANS mobile IQ
Software requirements
Required Android version
7.0 or higher
Required iOS version
12.0 or higher
Bluetooth
BLE 4.2 or higher
Technical specifications
9.8 Mobile IQ app and AW050 Bluetooth adapter
SIPART PS100
Compact Operating Instructions, 05/2021, A5E50188940-AA
49