Application planning
5
5.1
Supplementary electrical conditions
5.1.1
Grounding concept
Components
The SINUMERIK MC system consists of several individual components that have been
designed so that the system complies with the appropriate EMC and safety standards. The
individual system components are:
● Motion Control Unit MCU
● Machine Control Panel MCP
● Keyboard
● Operator panels
● S7-1500 I/O devices
Grounding measures
The individual modules are attached to a metal cabinet panel. Insulating paints on the mounting
points must be removed.
It is permissible to have a cluster of operator components for connection to the protective
conductor.
Example: Operator panel on the swivel arm.
In this case, it is sufficient to connect the protective conductor connectors of e.g. SINUMERIK
MCU and SIMATIC Panel for SINUMERIK to one another by a cable, and to lead a common
protective conductor to the central protective conductor connector in the control cabinet.
Further information
You can find further information at:
● Configuration Manual, EMC Guidelines
5.1.2
RI suppression measures
In addition to the protective grounding of system components, special precautions must be
taken to ensure safe, fault-free operation of the system. These measures include shielded
signal lines, special equipotential bonding connections, and isolation and shielding
measures.
MCU 1720
Equipment Manual, 09/2019, A5E47437728B AB
35
Summary of Contents for SINUMERIK MCU1720
Page 6: ...Table of contents MCU 1720 6 Equipment Manual 09 2019 A5E47437728B AB ...
Page 10: ...Preface MCU 1720 10 Equipment Manual 09 2019 A5E47437728B AB ...
Page 44: ...Dimension drawings 6 3 Portrait mounting MCU 1720 44 Equipment Manual 09 2019 A5E47437728B AB ...
Page 56: ...Installation 7 5 Mounting strain reliefs MCU 1720 56 Equipment Manual 09 2019 A5E47437728B AB ...
Page 96: ...Safety symbols MCU 1720 96 Equipment Manual 09 2019 A5E47437728B AB ...