Note
If your axis grouping contains a Smart Line Module without DRIVE-CLiQ (5 kW or 10 kW),
you must assign the Smart Line Module enabling signal to the X122.1 digital input on the
PPU.
Definition
The abbreviations used in "Signal type" column in the tables showing the pin assignment have
the following meaning:
B
Bidirectional
GND
Grounding
I
Input
O
Output
VI
Voltage input (supply voltage)
VO
Voltage output (supply voltage)
6.2
Power supply connection
6.2.1
Requirements for the power supply
Pin assignment at X1 screw-type terminal block
Table 6-1
Pin assignment
Pin
Signal name
Signal type Meaning
1
P24
VI
24 VDC power supply
2
M
VO
Ground
3
PE
GND
Protective ground
Requirements of DC power supplies
Interface X1 is intended exclusively for the connection of the external 24 V power supply, e.g.
● SITOP (stabilized 24 V power supplies)
● CSM (Control Supply Module)
The following power consumption values for the PPU provide a configuration basis for
calculating the 24 VDC power supply.
Interface description
6.2 Power supply connection
PPU
Manual, 01/2014, 6FC5397-2DP40-3BA3
69