SINAMICS V20 Converter
Operating Instructions, 10/2019, A5E34559884-012
23
Mechanical installation
3
Protection against the spread of fire
The device may be operated only in closed housings or in control cabinets with protective
covers that are closed, and when all of the protective devices are used. The installation of
the device in a metal control cabinet or the protection with another equivalent measure must
prevent the spread of fire and emissions outside the control cabinet.
Protection against condensation or electrically conductive contamination
Protect the device, e.g. by installing it in a control cabinet with degree of protection IP54
according to IEC 60529 or NEMA 12. Further measures may be necessary for particularly
critical operating conditions.
If condensation or conductive pollution can be excluded at the installation site, a lower
degree of control cabinet protection may be permitted.
3.1
Mounting orientation and clearance
The converter must be mounted in an enclosed electrical operating area or a control cabinet.
Mounting orientation
Always mount the converter vertically to a flat and non-combustible surface.