4.4.5
Checking the shock and tilt indicators inside the cabinet.
Shock and tilt indicators are also located inside the cabinet. Check these as soon as you have
unpacked and opened the device. To perform the check, proceed as described in "Checking
shock and tilt indicators"
NOTICE
Material damage caused by shipping indicators remaining in the device during operation
During operation, the shipping indicators can become detached and fall into the device as a
result of high temperatures. Material or temperature damage may result.
● Remove the shipping indicators before commissioning. Remove any adhesive residue
from the shipping indicators using methylated spirits.
See also
Checking shock and tilt indicators (Page 70)
4.5
Storage
4.5.1
Storing a device
If you are not going to commission the device immediately after delivery, ensure that it is stored
correctly.
Preconditions and preparations
● Store goods only in undamaged packaging. Unpack the goods if the packaging is damaged.
Correctly store the goods corresponding to the type of goods.
● Repair any damage to the packaging before putting the equipment into storage insofar as
this is necessary to ensure proper storage conditions.
Preparations for use
4.5 Storage
SINAMICS SM150 6SL3810-7NN38-0AA1
80