List of signals for the digital outputs
Signal
Bit in status word 1 Parameter
1 = Ready to switch on
0
r0889.0
1 = Ready to operate (DC link loaded, pulses blocked)
1
r0889.1
1 = Operation enabled (drive follows n_set)
2
r0889.2
1 = Fault present
3
r2139.3
0 = Coast to stop active (OFF2)
4
r0889.4
0 = Fast stop active (OFF3)
5
r0889.5
1 = Power-on disable
6
r0889.6
1 = Alarm present
7
r2139.7
1 = Speed setpoint/actual deviation in the tolerance bandwidth
(p2163, p2166)
8
r2197.7
1 = Control required to PLC
9
r0899.9
1 = f or n comparison value reached or exceeded (p2141, p2142) 10
r2199.1
1 = I, M, or P limit reached (p0640, p1520, p1521)
11
r1407.7
Reserved
12
0 = Alarm motor overtemperature (A7910)
13
r2129.14
Reserved
14
0 = Alarm thermal overload in power unit (A5000)
15
r2129.15
1 = Pulses enabled (inverter is clocking, drive is carrying current)
r0899.11
1 = n_act ≤ p2155
r2197.1
1 = n_act > p2155
r2197.2
1 = Ramp-up/ramp-down completed
r2199.5
1 = n_act < p2161 (preferably as n_min or n=0 message)
r2199.0
1 = Torque setpoint < p2174
r2198.10
1 = LOCAL mode active (control via operator panel)
r0807.0
0 = Motor blocked
r2198.6
1 = Ready to switch on
0
r0889.0
8.5.3
Monitoring functions and protective functions
The drive features hardware and software functions that protect it against faults and damage
caused by impermissible operating statuses or hardware malfunctions. The monitoring
elements provide internal microprocessor-controlled monitoring and remote device monitoring.
Operation
8.5 Functions
SINAMICS SM150 6SL3810-7NN38-0AA1
126