Communication
11.1 Communication according to PROFIdrive
Drive functions
760
Function Manual, 11/2017, 6SL3097-4AB00-0BP5
11.1.4.4
Example 1: read parameters
Requirements
●
The PROFIdrive controller has been commissioned and is fully operational.
●
PROFIdrive communication between the controller and the device is operational.
●
The controller can read and write data sets in conformance with PROFINET/PROFIBUS.
Task description
Following the occurrence of at least one fault (ZSW1.3 = "1") on drive 2 (also drive object
number 2), the active fault codes must be read from the fault buffer r0945[0] ... r0945[7].
The request is to be handled using a request and response data block.
Basic procedure
1.
Create a request to read the parameters.
2.
Invoke the request.
3.
Evaluate the response.
Create the request
Parameter request
Offset
Request header
Request reference = 25 hex
Request ID = 01 hex
0 + 1
Axis = 02 hex
Number of parameters = 01 hex
2 + 3
Parameter address
Attribute = 10 hex
Number of elements = 08 hex
4 + 5
Parameter no. = 945 dec
6
Subindex = 0 dec
8
Information about the parameter request:
●
Request reference:
The value is selected at random from the valid value range. The request reference
establishes the relationship between request and response.
●
Request ID:
01
hex → This identifier is
required for a read request.
●
Axis:
02
hex → Drive 2, fault buffer with drive
- and device-specific faults.
●
Number of parameters:
01
hex → One parameter is read.
●
Attribute:
10
hex → The parameter values are read.