Option L34 parameterizing the circuit breaker on the output side
Operating Instructions, 04/2014, A5E02914106A
11
Description
2
The option L34 (output-side circuit breaker) can be used to disconnect the motor terminals
from the converter.
This option is pre-wired and installed in a separate cabinet.
The option is described in the S120 Cabinet Modules Manual.
A script can be used for the automatic parameterization, which automatically makes the
parameter settings in STARTER.
For the automatic parameter setting of option L34, output-side circuit breaker, you will find
the script "output_side_circuit_breaker.xml" on the customer DVD supplied with the device.
To run the script, the following steps must be completely carried out in the completed project.
Free function blocks used
The following "free function blocks" are used in the script, and may not already be used in
the project:
●
MFP 0
●
AND 0
●
NOT 0
●
OR 0
●
PDF 0