Figure 7-6
Drive Output rebalanced using neutral shift
This neutral shift approach can be applied to more extreme situations.
Using neutral shift after loss of three cells
This example shows a 15 cell drive: five cells remain in phase A; one cell has failed in phase B; two
cells have failed in phase C.
Without neutral shift, all phases would need to be reduced to match the cell count of phase C to
maintain balanced motor voltages. 1 functional cell would be bypassed in phase B, and two
functional cells would be bypassed in phase A. Only 60% of the original cells would remain in
use, and only 60% of the original voltage would be available.
With neutral shift only the failed cells are bypassed. The phase angles of the cell voltages have
been adjusted so that phase A is displaced from phase B by 96.9° and from phase C by 113.1°,
instead of the normal 120°. The star-point of the cells no longer coincides with the neutral of the
motor voltages, but the motor voltage is balanced. 80% of the cells are in use, and 70% of full
voltage is available.
r
r
9&%
9%$
9$&
&
%
$
&
&
&
$
$
$
$
$
%
%
%
%
Figure 7-7
Drive Output after loss of 3 Cells
Operating the Control
7.4 Cell Bypass
Control Manual
188
Operating Manual, A5E50491925A
Summary of Contents for SINAMICS PERFECT HARMONY GH180
Page 2: ......
Page 22: ...Table of contents NXGPro Control Manual 20 Operating Manual A5E50491925A ...
Page 24: ...Security NXGPro Control Manual 22 Operating Manual A5E50491925A ...
Page 504: ...NEMA Table NXGPro Control Manual 502 Operating Manual A5E50491925A ...
Page 517: ...Index D NXGPro Control Manual Operating Manual A5E50491925A 515 ...
Page 518: ...Index NXGPro Control Manual 516 Operating Manual A5E50491925A ...
Page 530: ...Glossary NXGPro Control Manual 528 Operating Manual A5E50491925A ...
Page 537: ......