6.14
Options for Drive Protect Menu (7) - part 1
Note
Changing Drive Parameters
Only Siemens trained personnel are authorized to change drive parameters.
Familiarize yourself with the safety notes in Section Safety Notes for Parameter Changes and
preferentially contact Siemens customer service before changing the default configuration.
The Drive Protect Menu (7) consists of the following menu options:
• Input Protect Menu (7000)
• Single Phasing Menu (7010)
These menus are explained in the tables that follow.
Table 6-83
Drive Protect Menu (7) Parameters
Parameter
ID
Unit
Default
Min
Max
Description
Input protection 7000
Submenu
Access the input protection parameters.
See Table Input Protect Menu (7000).
Drive IOC set‐
point
7110
%
150.0
50.0
175.0
Drive instantaneous over current setpoint
as a percentage of drive output rating.
This parameter sets a hardware based
comparator threshold on the main control
board.
Cell Overload
Level
7112
%
100.0
100.0
150.0
Cell current overload, as a percentage of
drive output rating, allowed for 1 minute
out of every 10 minutes.
Power Rollback
Enable
7114
Enable
Enable
Disable
Enable Transformer Secondary Power Roll‐
back for bypass loading.
Auto reset ena‐
ble
7120
No
Enable the reset of the drive after a fault.
Auto reset time 7130
sec
1
0
120
Adjust the time between the fault and its
automatic reset.
Auto reset at‐
tempts
7140
4
1
10
Set the number of attempts a drive will be
reset before a permanent shutdown.
Auto reset
memory time
7150
sec
10
1
1000
Set the amount of time between faults
that will clear the attempts counter.
Fault Reset
7160
Function
Issue a drive fault reset when selected.
Thermal OT Roll‐
back
7170
Submenu
Thermal over temperature rollback sub‐
menu.
Refer to Section Thermal Over Tempera‐
ture Rollback for a description of opera‐
tion.
Min Rollback
Level
7171
Function
Minimum rollback level.
Rollback Ramp
Rate
7172
Function
Rollback base rate.
Parameter Assignment/Addressing
6.14 Options for Drive Protect Menu (7) - part 1
Control Manual
Operating Manual, A5E50491925A
153
Summary of Contents for SINAMICS PERFECT HARMONY GH180
Page 2: ......
Page 22: ...Table of contents NXGPro Control Manual 20 Operating Manual A5E50491925A ...
Page 24: ...Security NXGPro Control Manual 22 Operating Manual A5E50491925A ...
Page 504: ...NEMA Table NXGPro Control Manual 502 Operating Manual A5E50491925A ...
Page 517: ...Index D NXGPro Control Manual Operating Manual A5E50491925A 515 ...
Page 518: ...Index NXGPro Control Manual 516 Operating Manual A5E50491925A ...
Page 530: ...Glossary NXGPro Control Manual 528 Operating Manual A5E50491925A ...
Page 537: ......