Table 6-75
Incremental Speed Setup Menu (4970) Parameters
Parameter
ID
Unit
Default Min
Max
Description
Speed increment 1
4971
%
1.0
0.0
200.0
When selected through the SOP it will increase the
speed demand by the program amount.
Speed decrement 1
4972
%
1.0
0.0
200.0
When selected through the SOP it will decrease the
speed demand by the program amount.
Speed increment 2
4973
%
5.0
0.0
200.0
When selected through the SOP it will increase the
speed demand by the program amount.
Speed decrement 2
4974
%
5.0
0.0
200.0
When selected through the SOP it will decrease the
speed demand by the program amount.
Speed increment 3
4975
%
10.0
0.0
200.0
When selected through the SOP it will increase the
speed demand by the program amount.
Speed decrement 3
4976
%
10.0
0.0
200.0
When selected through the SOP it will decrease the
speed demand by the program amount.
Table 6-76
PID Select Menu (4350) Parameters
Parameter
ID
Unit
Default
Min
Max
Description
Prop gain
4360
0.39
0.0
98.996 Set the PID loop "Proportional (P) gain".
Integral gain
4370
0.39
0.0
98.996 Set the PID loop "Integral (I) gain".
Diff gain
4380
0.0
0.0
98.996 Set the PID loop "Derivative (D) gain".
Min clamp
4390
%
0.0
-200.0
200.0
Set the minimum value for the PID loop integrator.
Max clamp
4400
%
100.0
-200.0
200.0
Set the maximum value for the PID loop integrator.
Setpoint
4410
%
0.0
-200.0
200.0
Set a value to be used as the reference setpoint for the
external PID loop. The value is set as a percent of full
scale. This parameter can be used instead of Analog
Input #1 (4100) for reference in the PID loop.
Using a PID controller for speed reference
When using an external PID controller as the speed reference, analog input 1 (4100) or the set
point (4410) are used for PID command, and analog input 2 is used for PID feedback.
The input is pre-selected via the SOP.
See Tables Analog Input #1 Menu (4100) and Analog Input #2 Menu (4170) for scaling
information.
CAUTION
Providing correct inputs and parameters for PID command and feedback
If you assign incorrect inputs for PID command and feedback, it may cause instability of the
system and severe mechanical damage.
You are responsible for providing correct inputs and parameters for PID command and
feedback.
Check that all inputs and parameters for PID command and feedback are correctly assigned.
Parameter Assignment/Addressing
6.11 Options for Auto Menu (4)
Control Manual
146
Operating Manual, A5E50491925A
Summary of Contents for SINAMICS PERFECT HARMONY GH180
Page 2: ......
Page 22: ...Table of contents NXGPro Control Manual 20 Operating Manual A5E50491925A ...
Page 24: ...Security NXGPro Control Manual 22 Operating Manual A5E50491925A ...
Page 504: ...NEMA Table NXGPro Control Manual 502 Operating Manual A5E50491925A ...
Page 517: ...Index D NXGPro Control Manual Operating Manual A5E50491925A 515 ...
Page 518: ...Index NXGPro Control Manual 516 Operating Manual A5E50491925A ...
Page 530: ...Glossary NXGPro Control Manual 528 Operating Manual A5E50491925A ...
Page 537: ......