Flux Weakening
Flux in PU
0
0.2
0.4
0.6
0.8
1
1.2
1.4
1.6
1.8
0
10
20
30
40
50
60
70
80
90
100 110 120 130 140
Figure 6-5
Flux Weakening
Note
This feature is currently not implemented in
Table 6-55
Flux Table Menu (3131) Parameters
Parameter
ID
Unit
Default
Min
Max
Description
Flux Table Enable
3132
Off
Enables the flux shaping table
Flux @ 0.0% spd
3133
1.00
0.15
2.0
Flux demand at 0.0 percent of speed
Flux @ 0.5% spd
3134
1.00
0.15
2.0
Flux demand at 0.5 percent of speed
Flux @ 1.0% spd
3135
1.00
0.15
2.0
Flux demand at 1.0 percent of speed
Flux @ 1.5% spd
3136
1.00
0.15
2.0
Flux demand at 1.5 percent of speed
Flux @ 2.0% spd
3137
1.00
0.15
2.0
Flux demand at 2.0 percent of speed
Flux @ 2.5% spd
3138
1.00
0.15
2.0
Flux demand at 2.5 percent of speed
Flux @ 5.0% spd
3138
1.00
0.15
2.0
Flux demand at 5.0 percent of speed
Flux @ 10.0% spd
3140
1.00
0.15
2.0
Flux demand at 10.0 percent of speed
Flux @ 15.0% spd
3141
1.00
0.15
2.0
Flux demand at 15.0 percent of speed
Flux @ 20.0% spd
3142
1.00
0.15
2.0
Flux demand at 20.0 percent of speed
Flux @ 30.0% spd
3143
1.00
0.15
2.0
Flux demand at 30.0 percent of speed
Flux @ 40.0% spd
3144
1.00
0.15
2.0
Flux demand at 40.0 percent of speed
Speed at rated volts 3145 %
100.00
50.00
100.00
Percent of speed at which motor is at rated volts
Parameter Assignment/Addressing
6.8 Options for Stability Menu (3) - first half
Control Manual
Operating Manual, A5E50491925A
133
Summary of Contents for SINAMICS PERFECT HARMONY GH180
Page 2: ......
Page 22: ...Table of contents NXGPro Control Manual 20 Operating Manual A5E50491925A ...
Page 24: ...Security NXGPro Control Manual 22 Operating Manual A5E50491925A ...
Page 504: ...NEMA Table NXGPro Control Manual 502 Operating Manual A5E50491925A ...
Page 517: ...Index D NXGPro Control Manual Operating Manual A5E50491925A 515 ...
Page 518: ...Index NXGPro Control Manual 516 Operating Manual A5E50491925A ...
Page 530: ...Glossary NXGPro Control Manual 528 Operating Manual A5E50491925A ...
Page 537: ......