8.4 Up/Download
Intelligent Operating Panel 2 (IOP-2)
Operating Instructions, 06/2020, FW V2.6, A5E39549448B AH
55
Using the IOP-2
The IOP-2 must be handled with particular care for all SINAMICS devices that use an IOP-2 so
that no malicious software or erroneous parameterizations are spread between different
commissioning PCs or inverters.
WARNING
Risk of death due to software manipulation when using exchangeable storage media
Storing files onto exchangeable storage media amounts to an increased risk of infection of
the commissioning PCs, e.g. with viruses or malware. Incorrect parameter assignment can
cause machines to malfunction, which can lead to injuries or death.
•
Protect files stored on exchangeable storage media from malicious software using
appropriate protection measures, e.g. virus scanners.
WARNING
Risk of death due to software manipulation when using exchangeable storage media
Storing the parameterization (incl. Safety Integrated parameterization) on exchangeable
storage media carries the risk that the original parameterization (with Safety Integrated) will
be overwritten, for example, by the IOP-2 of another drive without Safety Integrated.
Incorrect parameter assignment can cause machines to malfunction, which can lead to
injuries or death.
•
Ensure that only the IOP-2 that belongs to the respective converter is used.
•
Ensure that only trained or authorized personnel have access to the enclosures, cabinets
or electrical equipment rooms.
Command Line Interface (CLI)
Overview
The CLI function allows the user to create a custom parameter listing and download the
listing directly to the drive using the IOP-2 download process.
The CLI file can be created using a suitable text editor, for example, the Windows Notepad
application. The format of the CLI is as follows:
wrp <number> <index> <value>
Where wrp is the command to write a parameter, followed by the parameter number, the
parameter index and the parameter value. For example, to write a parameter to the drive to
set the Ramp-up time to 5 seconds, the following format would be used:
wrp 1120 0 5.0
Each parameter in the listing must be on its own line, with no excess spaces between the
individual components of the command line, followed by a return.
Once the file has been created, the file should be stored on the IOP-2 in the
"user/cps"
folder
with the file extension cli, for example, ramp.cli.