6.8
Laying the signal lines
Malfunction due to common cable installation
Malfunctions can occur in the converter if cables with differing voltage levels are laid together
with internal cables in one cable duct in the cabinet.
● Do not run cables coming from the outside, for example to the terminal strips, together with
internal cables in one cable duct.
Ensure that the following instructions are complied with:
● All signal lines must be shielded. The cable shield should be braided, because cables
shielded by tape or foil are five times less efficiently protected against interference. Always
ground the cable shields at both ends. Contacting at one end is advantageous in
exceptional cases only.
● Clamp the shield of incoming analog and binary cables to the shield busbar at the entry point
into the cabinet. Continue running the cable, still shielded, to the terminal strip or board. No
shields are connected to the terminal strips or boards.
● Serial connecting cables must be shielded. Place the shield on the metallic connector
housing. Also connect the shield to the shield rail. Do not connect the cable shield to a
ground pin of the connector.
● The connector housing and front plate of the boards do not provide adequate cable
shielding. Connect the cable shields at both ends to the shield rails in the cabinets. Always
use shielded analog signal cables, regardless of whether they are installed inside or outside
cabinets. In order to increase the effectiveness of the shielding, ground spare conductors at
both ends.
6.9
Laying the cable shields
In the case of analog signal lines carrying small signals (mV or µA), attach the cable shield to
the shield bus in the cabinet at one end. In this way you avoid ground loops and line-frequency
interference. You can also connect the open shield end to the enclosure via a radio interference
suppression capacitor (e.g. 0.1 µF 100 V MKT).
6.10
Separating adjacent cabinets using unsuppressed contactors
Do not use any contactors without suppression in the converter cabinets or in cabinets that are
connected to the converter cabinets. All contactors installed in the factory are already equipped
with a suppression circuit. If you use unsuppressed contactors in an adjacent cabinet, you must
partition off the cabinets using a lateral metal plate.
Connect surge suppressors to contactor solenoids that are connected to the same line supply
as the auxiliary power supply of the converter – or are located near the converter (e.g. RC
elements, varistors).
Electrical connection
6.10 Separating adjacent cabinets using unsuppressed contactors
SINAMICS GL150 6SL38555UN113KA0Z
96
Operating Instructions Rev.201910281450 EXAMPLE
Summary of Contents for SINAMICS GL150
Page 2: ...28 10 2019 14 50 V18 00 ...
Page 162: ...Index SINAMICS GL150 6SL38555UN113KA0Z 162 Operating Instructions Rev 201910281450 EXAMPLE ...
Page 163: ......
Page 166: ......
Page 168: ......