Note
It is possible to toggle between command parameters (BICO parameters) using this data set changeover.
p0180
Number of Drive Data Sets (DDS) / DDS count
Access level: 3
Calculated: -
Data type: Unsigned8
Can be changed: C2(15)
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: 8565
Min:
1
Max:
4
Factory setting:
1
Description:
Sets the number of Drive Data Sets (DDS).
Dependency:
See also: p0010, r3996
NOTICE
When the data sets are created, short-term communication interruptions may occur.
r0200[0...n]
Power unit code number actual / PU code no. act
Access level: 3
Calculated: -
Data type: Unsigned16
Can be changed: -
Scaling: -
Dynamic index: PDS, p0120
Unit group: -
Unit selection: -
Function diagram: -
Min:
-
Max:
-
Factory setting:
-
Description:
Displays the unique code number of the power unit.
Note
r0200 = 0: No power unit data found
p0201[0...n]
Power unit code number / PU code no
Access level: 3
Calculated: -
Data type: Unsigned16
Can be changed: C2(2)
Scaling: -
Dynamic index: PDS, p0120
Unit group: -
Unit selection: -
Function diagram: -
Min:
0
Max:
65535
Factory setting:
0
Description:
Sets the actual code number from r0200 to acknowledge the power unit being used.
When commissioned for the first time, the code number is automatically transferred from r0200 into p0201.
Note
The parameter is used to identify when the drive is being commissioned for the first time.
The power unit commissioning can only be exited (p0201 = r0200), if the actual and acknowledged code numbers are
identical (p0010 = 2).
When the code number is changed, the connection voltage (p0210) is checked and, if necessary, adjusted.
r0203[0...n]
Actual power unit type / PU actual type
Access level: 3
Calculated: -
Data type: Integer16
Can be changed: -
Scaling: -
Dynamic index: PDS, p0120
Unit group: -
Unit selection: -
Function diagram: -
Min:
2
Max:
400
Factory setting:
-
Description:
Displays the type of power unit found.
Value:
2:
MICROMASTER 440
3:
MICROMASTER 411
4:
MICROMASTER 410
Parameters
7.3 Parameters
SINAMICS G120XA converter