6.3.5
Cavitation protection
Overview
Cavitation problem can damage the impeller of the pumps, reduce the output water flow and
cause unexpected noise. The cavitation protection will generate a fault/warning when
cavitation conditions are deemed to be present. If the converter gets no feedback from the
pump transducer, it will trip to prevent cavitation damage. This function saves the maintenance
efforts and extends the lifetime expectancy of the system.
Function description
&DYLWDWLRQSURWHFWLRQHQDEOH
3,'6FDOHG
IHHGEDFN>@
6WDWXVZRUGELW3,'PLQLPXPOLPLWUHDFKHG
6WDWXVZRUGELW3,'PD[LPXP
OLPLWUHDFKHG
6WDWXVZRUGELW3,'LQYHUWHUUXQQLQJ
&DYLWDWLRQSURWHFWLRQGHOD\
3,'HQDEOHGLVDEOH
&DYLWDWLRQSURWHFWLRQWKUHVKROG
>@
7ULJJHUZDUQLQJ$
7ULJJHUIDXOW)
&DYLWDWLRQSURWHFWLRQGLVDEOHG
S
S
U
U
U
>V@
U
7
ุ
S
S
Parameters
Number
Name
Factory setting
p29625
Cavitation protection enable
0
p29626
Cavitation protection threshold
40%
p29627
Cavitation protection time
30 s
For more information about the parameters, see Chapter "Parameters (Page 349)".
Advanced commissioning
6.3 Pump control
SINAMICS G120XA converter
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB
221