p29622[0...n]
BI: Frost protection enable / Fro en
Access level: 3
Calculated: -
Data type: Unsigned32 / Binary
Can be changed: T, U
Scaling: -
Dynamic index: CDS, p0170
Unit group: -
Unit selection: -
Function diagram: -
Min:
-
Max:
-
Factory setting:
0
Description:
Sets the signal source to enable frost protection. If the binary input is equal to 1, then protection will be initiated. If the
converter is stopped and the protection signal becomes active, protection measure is applied as follows:
- If p29623 != 0, frost protection is activated by applying the specified speed to the motor;
- If p29623 = 0, and p29624 != 0, condensation protection is activated by applying the specified current to the motor.
Note
The protection function may be overridden under the following conditions:
- If the converter is running and the protection signal becomes active, the signal is ignored.
- If the converter is turning a motor due to active protection signal and a RUN command is received, RUN command
overrides the frost protection signal.
- Issuing an OFF command while protection is active will stop the motor.
p29623[0...n]
Frost protection speed / Fro spd
Access level: 3
Calculated: -
Data type: FloatingPoint32
Can be changed: T, U
Scaling: p2000
Dynamic index: DDS, p0180
Unit group: 3_1
Unit selection: p0505
Function diagram: -
Min:
-210000.000 [rpm]
Max:
210000.000 [rpm]
Factory setting:
0.000 [rpm]
Description:
Specifies the speed applied to the motor when frost protection is active.
And this parameter can't be changed when the frost or condensation function is active.
Dependency:
See also p29622.
p29624[0...n]
Condensation protection current / Cond current
Access level: 3
Calculated: -
Data type: FloatingPoint32
Can be changed: T, U
Scaling: -
Dynamic index: DDS, p0180
Unit group: -
Unit selection: -
Function diagram: -
Min:
0.000 [%]
Max:
100.000 [%]
Factory setting:
30.000 [%]
Description:
Specifies the DC current (as a percentage of rated current) applied to the motor when condensation protection is
active.
Dependency:
See also p29622.
Note
The change to the current becomes effective the next time condensation protection is active.
p29625[0...n]
Cavitation protection enable / Cavi en
Access level: 3
Calculated: -
Data type: Integer16
Can be changed: T, U
Scaling: -
Dynamic index: DDS, p0180
Unit group: -
Unit selection: -
Function diagram: -
Min:
0
Max:
2
Factory setting:
0
Description:
Enables the cavitation protection function. A fault/alarm is generated when cavitation conditions are deemed to be
present.
Value:
0:
The cavitation protection function is deactivated
1:
The cavitation protection function triggers fault F52960
2:
The cavitation protection function triggers warning A52961