p2293
Technology controller ramp-up/ramp-down time / Tec_ctr t_RU/RD
Access level: 3
Calculated: -
Data type: FloatingPoint32
Can be changed: T, U
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: 7958
Min:
0.00 [s]
Max:
100.00 [s]
Factory setting:
1.00 [s]
Description:
Sets the ramping time for the output signal of the technology controller.
Dependency:
See also: p2291, p2292
Note
The time refers to the set maximum and minimum limits (p2291, p2292).
r2294
CO: Technology controller output signal / Tec_ctrl outp_sig
Access level: 2
Calculated: -
Data type: FloatingPoint32
Can be changed: -
Scaling: PERCENT
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: 7958
Min:
- [%]
Max:
- [%]
Factory setting:
- [%]
Description:
Display and connector output for the output signal of the technology controller.
Dependency:
See also: p2295
p2295
CO: Technology controller output scaling / Tec_ctrl outp scal
Access level: 3
Calculated: -
Data type: FloatingPoint32
Can be changed: T, U
Scaling: PERCENT
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: 7958
Min:
-100.00 [%]
Max:
100.00 [%]
Factory setting:
100.00 [%]
Description:
Sets the scaling for the output signal of the technology controller.
p2296[0...n]
CI: Technology controller output scaling / Tec_ctrl outp scal
Access level: 3
Calculated: -
Data type: Unsigned32 /
FloatingPoint32
Can be changed: T, U
Scaling: PERCENT
Dynamic index: CDS, p0170
Unit group: -
Unit selection: -
Function diagram: 7958
Min:
-
Max:
-
Factory setting:
2295[0]
Description:
Sets the signal source for the scaling value of the technology controller.
Dependency:
See also: p2295
p2297[0...n]
CI: Technology controller maximum limit signal source / Tec_ctrMaxLim s_s
Access level: 3
Calculated: -
Data type: Unsigned32 /
FloatingPoint32
Can be changed: T, U
Scaling: PERCENT
Dynamic index: CDS, p0170
Unit group: -
Unit selection: -
Function diagram: 7958
Min:
-
Max:
-
Factory setting:
1084[0]
Description:
Sets the signal source for the maximum limiting of the technology controller.
Dependency:
See also: p2291
Parameters
7.2 Parameter list
SINAMICS G120X converter
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
807