p0731
BI: CU signal source for terminal DO 1 / CU s_s DO 1
Access level: 2
Calculated: -
Data type: Unsigned32 / Binary
Can be changed: T, U
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: 2119, 2030,
2130
Min:
-
Max:
-
Factory setting:
52.2
Description:
Sets the signal source for terminal DO 1 (NO: X134. 24 / NC: X134. 23).
Recommendation:
r0052.0 Ready for switching on
r0052.1 Ready for operation
r0052.2 Operation enabled
r0052.3 Fault present
r0052.4 Coast down active (OFF2)
r0052.5 Quick stop active (OFF3)
r0052.6 Switching on inhibited active
r0052.7 Alarm present
r0052.9 Control request
r0052.14 Motor rotates forwards
r0053.0 DC braking active
r0053.1 n_act > p2167 (n_off)
r0053.2 n_act <= p1080 (n_min)
r0053.3 I_act > p2170
r0053.4 n_act > p2155
r0053.5 n_act <= p2155
r0053.6 n_act >= n_set
r0053.10 Technology controller output at the lower limit
r0053.11 Technology controller output at the upper limit
NOTICE
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Note
DO: Digital Output
Relay output: NO = normally open, NC = normally closed
p0732
BI: CU signal source for terminal DO 2 / CU s_s DO 2
Access level: 2
Calculated: -
Data type: Unsigned32 / Binary
Can be changed: T, U
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: 2119, 2030,
2130
Min:
-
Max:
-
Factory setting:
52.0
Description:
Sets the signal source for terminal DO 2 (NO: X204. 98 / NC: X204. 99).
Parameters
7.2 Parameter list
SINAMICS G120X converter
562