400 V Converter
frame size
Rated power (kW)
Line harmonics filter
FSD
18.5
UAC:FN344019113E2FAJRX
22
UAC:FN344022115E2FAJRX
30
UAC:FN344030115E2FAJRX
37
UAC:FN344037115E2FAJRX
FSE
45
UAC:FN344045115E2FAJRX
55
UAC:FN344055115E2FAJRX
FSF
75
UAC:FN344075116E2FAJRX
90
UAC:FN344090116E2FAJRX
110
UAC:FN3440110118E2FAJRX
132
UAC:FN3440132118E2FAJXX
FSG
160
UAC:FN3440160118E2FAJXX
200
UAC:FN3440200118E2FAJXX
250
2x UAC:FN3440132118E2FAJXX
*)
*)
Parallel connection between two line harmonics filters with 132 kW each
The converters FSA are not assigned to a line harmonics filter. If the rated power of the line
harmonics filter is not exceeded, you may operate several convertors FSA on a common line
harmonics filter.
Special restrictions for converter FSG
When connecting 400 V converter FSG with line harmonics filters, parameter p1300 must be
set to 20.
For converter FSG with line harmonics filter, operation is only permissible in the vector control
mode. It is not permissible for U/f mode to be used.
2.6.4
Output reactor
Note
Output reactors are available as optional components for converters FSD ... FSJ.
The output reactor reduces the voltage rate of rise and dampens transient voltage peak at the
converter output, and enable longer motor cables to be connected.
Description
2.6 Optional components
SINAMICS G120X converter
36
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC