Data exchange with the client
The converter receives control commands and setpoints via service instructions from the
control and transmits its status back to the control. The converter can also send telegrams
automatically itself, respectively execute services, e.g. COV_Notification.
The converter supports Unicode, coded with character set UTF-8
Further information
The Protocol Implementation Conformance Statement (PICS) is available on the Internet:
http://www.big-eu.org/uploads/tx_teproddb/catalog_pdf/
PICS_CU230P-2_HVAC_v47_SP3.docx
6.3.7.2
Activating communication via fieldbus
Function description
Procedure
Proceed as follows to activate communication via BACnet MS/TP:
1. Start quick commissioning.
Quick commissioning using the BOP-2 operator panel (Page 159)
2. In the first steps of the quick commissioning, confirm all of the values that have already been
set.
3. Select the default setting 54: "USS control".
Default setting of the interfaces (macros) (Page 107)
4. In the next steps of the quick commissioning, confirm all additional values that have already
been set.
5. Exit quick commissioning.
6. Set p2030 = 5
You have activated communication via BACnet MS/TP.
❒
ON/OFF commands via BACnet
Selecting the macro 54 has the following effect:
● Only the ON/OFF2 command is possible via the terminal strip.
● The higher-level controller cannot turn the motor on or off.
To turn the motor on and off via the higher-level controller, you need to manually interconnect
the ON/OFF1 and OFF2 commands with the PROFIdrive control word:
● Set p0840[0] = r2090.0
● Set p0844[0] = r2090.1