4.2.6
Default setting of the interfaces (macros)
Overview
The function of most of the converter terminals can be set.
In order to avoid having to successively change terminal for terminal, multiple terminals can be
set jointly for quick commissioning. Parameter p0015 for quick commissioning initiates a macro
that adopts the setting of the terminals.
Table 4-9
Overview of default settings, Part 1/2
Default setting (macro)
Terminal
41
42
43
44
45
46
1)
47
AI 0
Setpoint
Setpoint
Setpoint
Setpoint
Setpoint
Setpoint local
-
AI 1
-
PID actual
value
PID actual
value
PID actual
value
-
Setpoint re‐
mote
PID actual
value
AO 0 Speed actual
value
Speed actual
value
Speed actual
value
Speed actual
value
Speed actual
value
Speed actual
value
Speed actual
value
AO 1
2)
Current ac‐
tual value
Current ac‐
tual value
Current ac‐
tual value
Current ac‐
tual value
Current ac‐
tual value
Current ac‐
tual value
Current ac‐
tual value
DI 0
ON/OFF2
ON/OFF2
ON/OFF2
ON/OFF2
ON/OFF2
ON/OFF2 lo‐
cal
ON/OFF2
DI 1
-
-
Service pump
1
Service pump
1
Fixed set‐
point 1
ON/OFF2 re‐
mote
-
DI 2
-
-
Service pump
2
Service pump
2
Fixed set‐
point 2
-
-
DI 3
-
-
-
Service pump
3
Fixed set‐
point 3
-
-
DI 4
-
manual ↔ au‐
to
manual ↔ au‐
to
manual ↔ au‐
to
-
local ↔ remote
-
DI 5 Acknowledge
fault
Acknowledge
fault
Acknowledge
fault
Acknowledge
fault
Acknowledge
fault
Acknowledge
fault
Acknowledge
fault
DO 0
Fault
Fault
Fault
Fault
Fault
Fault
Fault
DO 1
Operation
Operation
Operation
Pump 1
Operation
Operation
Operation
DO 2
2)
Ready for op‐
eration
Ready for op‐
eration
Pump 1
Pump 2
Ready for op‐
eration
Ready for op‐
eration
Ready for op‐
eration
DO 3
2)
Alarm
Alarm
Pump 2
Pump 3
Alarm
Alarm
Alarm
Fieldbus
-
-
-
-
-
-
-
1)
For converters with USS fieldbus interfaces
2)
With I/O Extension Module
Wiring
4.2 Control interfaces
SINAMICS G120X converter
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
107