No.
Description
86 hex
Write access only for commissioning (p0010 = 15) (operating state of the converter prevents
a parameter change)
87 hex
Know-how protection active, access locked
C8 hex
Change request below the currently valid limit (change request to a value that lies within the
"absolute" limits, but is however below the currently valid lower limit)
C9 hex
Change request above the currently valid limit (example: a parameter value is too large for
the converter power)
CC hex
Change request not permitted (change is not permitted as the access code is not available)
PNU (parameter number) and page index
Parameter number
PNU
Page index
0000 … 1999
0000 … 1999
0 hex
2000 … 3999
0000 … 1999
80 hex
6000 … 7999
0000 … 1999
90 hex
8000 … 9999
0000 … 1999
20 hex
10000 … 11999
0000 … 1999
A0 hex
20000 … 21999
0000 … 1999
50 hex
30000 … 31999
0000 … 1999
F0 hex
60000 … 61999
0000 … 1999
74 hex
Subindex
For indexed parameters, the parameter index is located in subindex as hexadecimal value.
PWE: Parameter value or connector
Parameter values or connectors can be located in the PWE.
Table 6-12
Parameter value or connector
PWE 1
PWE 2
Parameter value
Bit 15 … 0
Bit 15 … 8
Bit 7 … 0
0
0
8-bit value
0
16-bit value
32-bit value
Connector
Bit 15 … 0
Bit 15 … 10
Bit 9 … 0
Number of the connector
3F hex
The index or bit field
number of the connec‐
tor
Advanced commissioning
6.3 Drive control
SINAMICS G120X converter
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
215