11.4
Technical data dependent on the power
3-phase 380 … 480 V AC
Frame
size
Rated
power
[kW] (NEC
[hp])
Rated in‐
put current
[A] (NEC
480 V)
Rated output
current [A]
(NEC 480 V)
Power
[kW]
(NEC
[hp])
Input cur‐
rent [A]
(NEC
480 V)
Output
current
[A] (NEC
480 V)
Power loss (kW) Net weight (kg)
Based on Low Overload
Based on High Overload
With‐
out fil‐
ter
With fil‐
ter
With‐
out fil‐
ter
With fil‐
ter
FSA
0.75 (1)
2.1 (2.0)
2.2 (2.1)
0.55
(0.75)
1.7 (1.6)
1.7 (1.6)
0.043
0.043
3.3
3.5
1.1 (1.5)
2.8 (2.7)
3.1 (3.0)
0.75 (1)
2.1 (2.0)
2.2 (2.1)
0.055
0.055
3.3
3.5
1.5 (2)
3.6 (3.0)
4.1 (3.4)
1.1 (1.5)
2.8 (2.7)
3.1 (3.0)
0.071
0.072
3.3
3.5
2.2 (3)
5.5 (4.6)
5.9 (4.8)
1.5 (2)
3.6 (3.0)
4.1 (3.4)
0.090
0.091
3.4
3.6
3 (4)
6.9 (5.8)
7.7 (6.2)
2.2 (3)
5.5 (4.6)
5.9 (4.8)
0.123
0.125
3.4
3.6
FSB
4 (5)
9.75
10.2 (7.6)
3 (4)
7.75
7.7 (6.2)
0.136
0.138
5.8
6.2
5.5 (7.5)
12
13.2 (11)
4 (5)
9.75
10.2 (7.6) 0.18
0.183
5.8
6.2
7.5 (10)
17
18 (14)
5.5 (7.5)
13.25
13.2 (11)
0.245
0.253
5.8
6.2
FSC
11 (15)
24.5
26 (21)
7.5 (10)
18.25
18 (14)
0.316
0.32
7.1
7.7
15 (20)
29.5
32 (27)
11 (15)
24.5
26 (21)
0.396
0.402
7.1
7.7
FSD
18.5 (25)
36 (32)
38 (34)
15 (20)
33 (28)
32 (27)
0.59
0.60
16.6
18.3
22 (30)
42 (37)
45 (40)
18.5 (25) 38 (35)
38 (34)
0.72
0.73
16.6
18.3
30 (40)
57 (49)
60 (52)
22 (30)
47 (41)
45 (40)
0.83
0.84
16.6
18.3
37 (50)
70 (61)
75 (65)
30 (40)
62 (54)
60 (52)
1.10
1.11
18.8
19.5
FSE
45 (60)
86 (74)
90 (77)
37 (50)
78 (69)
75 (65)
1.33
1.34
17.6
18.3
55 (75)
104 (91)
110 (96)
45 (60)
94 (80)
90 (77)
1.73
1.71
26.7
28.7
FSF
75 (100)
140 (120)
145 (124)
55 (75)
117 (102) 110 (96)
1.97
2.00
61
67.5
90 (125)
172 (151)
178 (156)
75 (100)
154 (132) 145 (124) 2.57
2.61
61
67.5
110 (150)
198 (174)
205 (180)
90 (125)
189 (166) 178 (156) 2.37
2.41
66.5
71
132 (200)
241 (232)
250 (240)
110 (150) 218 (191) 205 (180) 3.10
3.16
66.5
71
FSG
160 (250)
301 (301)
302 (302)
132 (200) 275 (263) 250 (240) 3.22 *
3.66 **
--
105
200 (300)
365 (356)
370 (361)
160 (250) 330 (327) 302 (302) 4.61 *
4.61 **
--
113
250 (400)
471 (471)
477 (477)
200 (300) 400 (392) 370 (361) 6.17 *
6.17 **
--
120
FSH
315 (---)
585 (486)
570 (477)
250 (300) 477 (397) 468 (390) --
6.79
--
151
355 (450)
654 (525)
640 (515)
250 (300) 501 (402) 491 (394) --
7.69
--
157
400 (500)
735 (602)
720 (590)
315 (350) 562 (461) 551 (452) --
8.39
--
159
FSJ
450 (---)
850 (687)
820 (663)
355 (450) 696 (561) 672 (542) --
10.42
--
235
500 (600)
924 (751)
890 (724)
400 (500) 756 (614) 728 (591) --
10.89
--
250
560 (700)
1038 (862) 1000 (830)
450 (500) 816 (677) 786 (652) --
12.50
--
250
* With C3 filter
** With C2 filter
--- not applicable
Technical data
11.4 Technical data dependent on the power
SINAMICS G120X converter
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
1089