Technical data
11
11.1
Technical data of inputs and outputs
Property
Explanation
Fieldbus interface (depending
on the Control Unit)
PROFINET
USS
PROFIBUS DP
24 V power supply
There are two options regarding the 24 V supply:
● The converter generates its 24 V power supply from the line voltage.
● The converter obtains its 24 V power supply via terminals 31 and 32 with 20.4 … 28.8
VDC. Current consumption: Maximum 0.5A (The current consumption can be higher if
the Control Unit supplies I/O extension module, additional 0.4 A is needed.)
Output voltages
● 24 V (max. 250 mA)
● 10 V (max. 10 mA)
Setpoint resolution
0.01 Hz
Digital inputs
6 (DI 0 … DI 5)
● Electrically isolated
● Type 3 in accordance with EN 61131-2
● Voltage for "low" state: < 5 V
● Voltage for "high" state: > 11 V
● Current for 24 V input voltage: 4 mA
● Minimum current for the "high" state: 2.5 mA
● Maximum input voltage: 30 V
● PNP/NPN switchable
● Compatible to SIMATIC outputs
● 10 ms response time for debounce time p0724 = 0
Additional on FSH,
FSJ:
4 (DI 0 … DI 3)
● Electrically isolated
● Type 3 in accordance with EN 61131-2
● Voltage for "low" state: < 5 V
● Voltage for "high" state: > 15 V
● Current for 24 V input voltage: 6.4 mA
● Minimum current for the "high" state: 4 mA
● Maximum input voltage: 30 V
SINAMICS G120X converter
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
1081