Appendix
7.2 Definition of the EMC Environment and Categories
PM230 Power Module IP55
Hardware Installation Manual, 11/2014, A5E35319202B AA
85
Category C3
Power Drive System (PDS) of rated voltage less than 1000 V intended for use in the Second
(Industrial) Environment and not intended for use within the First (Domestic) Environment.
Table 7- 1
Compliance Table
Model
Remarks
Category C1 - First Environment
--
The inverters with integrated Class B filters meet the requirements for
category C1 for conducted emissions.
Category C2 - First Environment - Professional Use
Filtered Variants
6SL3223-0DE**-*A** (integrated class A filter)
6SL3223-0DE**-*B** (integrated class B filter)
Class A: 25 m screened cable type CY
All units have integrated Class A or Class B filters
When used in the First Environment this product may cause radio inter-
ference in which case mitigation measures may be required. Units require
supply authority acceptance for connection to the public low-voltage pow-
er supply network. Please contact your local supply network provider.
Category C3 - Second Environment
Unfiltered Variants
There are not unfiltered variants of the PM230 Power Module
Note
All drives should be installed and commissioned in accordance with the manufacturer’s
guidelines and in accordance with good EMC practices.
For further information refer to SIEMENS application note "EMC Design Guidelines".