Technical specifications
6.2 Temperature, altitude and voltage derating PM230
PM230 Power Module IP55
Hardware Installation Manual, 11/2014, A5E35319202B AA
75
Feature
Version
Relative humidity
< 95% - condensation not permissible
Contamination
Protected from contact with dangerous parts, dust, spray water and water jets
Environmental requirements Protected against damaging chemical substances according to environmental class 3C2 to
EN 60721-3-3: 1995
Shock and vibration
•
Long-term storage in the transport packaging according to Class 1M2 to EN 60721-3-1:
1997
•
Transport in the transport packaging according to Class 2M3 to EN 60721-3-2: 1997
•
Vibration during operation according to Class 3M2 to EN 60721-3-3: 1995
Installation altitude
without derating:
with derating:
up to 1000 m above sea level
up to 4000 m above sea level
Derating see Temperature, altitude and voltage derating PM230 (Page 75)
Rated short-circuit current
When fused using a type J or 3NE1 fuse, rated voltage 480 V AC
with the rated current of the specific inverter.
FSA ... FSC: 40 kA
FSD ... FSF: 65 kA
6.2
Temperature, altitude and voltage derating PM230
Operating temperature derating
The operating temperature range is shown diagramatically in the figures below:
Figure 6-2
Current derating for temperature PM230 FSA ... FSF