SINAMICS G120D
List Manual (LH14), 01/2016, A5E33842313
25
2 Parameters
2.2 List of parameters
2.2
List of parameters
Product: SINAMICS G120D, Version: 4707900, Language: eng
Objects: CU240D-2_DP, CU240D-2_PN, CU240D-2_DP_F, CU240D-2_PN_F, CU250D-2_PN_F, CU250D-2_DP_F
Description:
Operating display for the drive.
Value:
0:
Operation - everything enabled
10:
Operation - set "enable setpoint" = "1" (p1142)
12:
Operation - RFG frozen, set "RFG start" = "1" (p1141)
13:
Operation - set "enable RFG" = "1" (p1140)
14:
Operation - MotID, excit. running
15:
Operation - open brake (p1215)
16:
Operation - withdraw braking with OFF1 using "ON/OFF1" = "1"
17:
Operation - braking with OFF3 can only be interrupted with OFF2
18:
Operation - brake on fault, remove fault, acknowledge
19:
Operation - DC braking active (p1230, p1231)
21:
Ready for operation - set "Operation enable" = "1" (p0852)
22:
Ready for operation - de-magnetizing running (p0347)
31:
Ready for switching on - set "ON/OFF1" = "0/1" (p0840)
35:
Switching-on inhibited - carry out first commissioning (p0010)
41:
Switching-on inhibited - set "ON/OFF1" = "0" (p0840)
42:
Switching-on inhibited - set "OC/OFF2" = "1" (p0844, p0845)
43:
Switching-on inhibited - set "OC/OFF3" = "1" (p0848, p0849)
44:
Switching-on inhibited - supply STO terminal w/ 24 V (hardware)
45:
Switching-on inhibited - rectify fault, acknowledge fault, STO
46:
Switching-on inhibited - exit commissioning mode (p0010)
70:
Initialization
200:
Wait for booting/partial booting
Dependency:
Refer to: r0046
Notice:
For several missing enable signals, the corresponding value with the highest number is displayed.
Note:
OC: Operating condition
RFG: Ramp-function generator
COMM: Commissioning
MotID: Motor data identification
Description:
Sets the access level to read and write parameters.
Value:
3:
Expert
4:
Service
Note:
A higher set access level also includes the lower one.
Access level 3 (experts):
Expert know-how is required for these parameters (e.g. BICO parameterization).
Access level 4 (service):
For these parameters, it is necessary that authorized service personnel enter the appropriate password (p3950).
r0002
Drive operating display / Drv op_display
Access level:
2
Calculated:
-
Data type:
Integer16
Can be changed:
-
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
0 200
-
p0003
Access level / Acc_level
Access level:
1
Calculated:
-
Data type:
Integer16
Can be changed:
C, U, T
Scaling:
-
Dyn. index:
-
Unit group:
-
Unit selection:
-
Func. diagram:
-
Min Max
Factory
setting
3 4 3