SINAMICS G120D
List Manual (LH14), 01/2016, A5E33842313
15
2 Parameters
2.1 Overview of parameters
Access level
Specifies the minimum access level required to be able to display and change the relevant
parameter. The required access level can be set using p0003.
The system uses the following access levels:
•
1: Standard (not adjustable, included in p0003 = 3)
•
2: Extended (not adjustable, included in p0003 = 3)
•
3: Expert
•
4: Service
Parameters with this access level are password protected.
Calculated
Specifies whether the parameter is influenced by automatic calculations.
p0340 determines which calculations are to be performed:
•
p0340 = 1 includes the calculations from p0340 = 2, 3, 4, 5.
•
p0340 = 2 calculates the motor parameters (p0350 ... p0360, p0625).
•
p0340 = 3 includes the calculations from p0340 = 4, 5.
•
p0340 = 4 only calculates the controller parameters.
•
p0340 = 5 only calculates the controller limits.
Parameters with a reference to p0340 after "Calculated" depend on the Power Module being
used and the motor. In this case, the values at "Factory setting" do not correspond to the actual
values because these values are calculated during the commissioning. This also applies to the
motor parameters.
Note
Parameter p0003 is CU-specific (belongs to the Control Unit).
A higher access level will also include the functions of the lower levels.
Note:
For p3900 > 0, p0340 = 1 is also called automatically.
After p1900 = 1, 2, p0340 = 3 is also called automatically.