Technical data
6.5 400 V converters
Power Module PM240-2
Hardware Installation Manual, 01/2020, A5E33294624B AL
89
Dependency of input voltage and output power
6.5.2
Specific technical data, 400 V converters
Table 6- 15 PM240-2, IP20, frame size A, 380 V … 480 V 3 AC
Article No. without filter
Article No. with filter
6SL3210-1PE11-8UL1
6SL3210-1PE11-8AL1
6SL3210-1PE12-3UL1
6SL3210-1PE12-3AL1
6SL3210-1PE13-2UL1
6SL3210-1PE13-2AL1
LO base load power
0.55 kW
0.75 kW
1.1 kW
LO base load input current
2.3 A
2.9 A
4.1 A
LO base load output current
1.7 A
2.2 A
3.1 A
HO base load power
0.37 kW
0.55 kW
0.75 kW
HO base load input current
2.0 A
2.6 A
3.3 A
HO base load output current
1.3 A
1.7 A
2.2 A
Fuse according to IEC
Fuse according to UL, class J
3NA3805 (16 A)
10 A
3NA3805 (16 A)
10 A
3NA3805 (16 A)
15 A
Power loss
0.04 kW
0.04 kW
0.04 kW
Required cooling air flow
5 l/s
5 l/s
5 l/s
Weight without filter
1.3 kg
1.3 kg
1.3 kg
Weight with filter
1.5 kg
1.5 kg
1.5 kg