Technical data
10.8 Electromagnetic Compatibility
Converter with the control units CU240D-2
318
Operating Instructions, 04/2018, FW V4.9 SP10, A5E34262100B AF
Table 10- 7 Conducted disturbance voltage and radiated emissions
EMC Phenomenon
Converter type
Remark
Level acc. to
IEC 61800-3
Conducted emissions
(disturbance voltage)
All converters with integrated class A filters.
Article number:
6SL3525-0PE . . - . A . .
Category C2
First Environment -
Professional Use
Radiated emissions
Converter frame sizes A, B and C with integrated
class A filter.
Article number:
6SL3525-0PE17- . A . .
6SL3525-0PE21- . A . .
6SL3525-0PE23- . A . .
6SL3525-0PE24- . A . .
6SL3525-0PE25- . A . .
6SL3525-0PE27- . A . .
In a domestic environment this product may cause
radio interference in which case supplementary miti-
gation measures may be required.
Category C2
First Environment -
Professional Use
Harmonic Currents
Table 10- 8 Harmonic Currents
Typical Harmonic Current (% of rated input current) at U
K
1 %
5th
7th
11th
13th
17th
19th
23rd
25th
54
39
11
5
5
3
2
2
Units installed within the category C2 (domestic) environment require supply authority
acceptance for connection to the public low-voltage power supply network. Please contact
your local supply network provider.
Units installed within the category C3 (industrial) environment do not require connection
approval.
EMC Immunity
The SINAMICS G120D drives have been tested in accordance with the immunity
requirements of category C3 (industrial) environment.
The immunity requirements apply equally to both filtered and unfiltered units.
Table 10- 9 EMC Immunity
EMC Phenomenon
Standard
Level
Performance
Criterion
Electrostatic Discharge (ESD)
EN 61000-4-2
4 kV Contact discharge
A
8 kV Air discharge