Technical specifications
8.4 Technical data
SINAMICS CONNECT
86
Operating Instructions, 10/2018, A5E45421408
Motherboard
Processor
Intel Quark X1020, 400 MHz
RAM
1 GB
BIOS SPI Flash
8 MB
Micro SD
Slot for one Micro SD card
Interfaces
LAN interface X1 P1, RJ45
1)
SOC LAN controller
LAN interface X2 P1, RJ45
2)
SOC LAN controller
RS232 ports X121, X122
RS 232, ≤ 115 Kbps, terminal block,
17-pin
Maximum permitted cable length: 3 m
1)
Termination can be set with the software.
2)
For unique labeling, the LAN interfaces are numbered on the enclosure. The numbering by the
operating system can differ.
8.4.2
Ambient conditions
Climatic ambient conditions
The temperature values have been checked in accordance with IEC 60068-2-1, IEC 60068-
2-2 and IEC 60068-2-14. For more information about permitted mounting positions, see
Section "Permitted mounting orientation and mounting types (Page 24)".
Ambient temperature
Operation
0 °C to 50 °C
1)
Storage/transport
-
20 °C to 70
°C
Gradient
Operation
≤ 10 °C/h
Storage
20 °C/h, no condensation
Relative humidity, tested in accordance with IEC 60068-2-78, IEC 60068-2-30
Operation
5% to 85% at 30 °C, no condensation
Storage/transport
5% to 95% at 25/55 °C, no condensation
Atmospheric pressure
Operation
1080 hPa to 795 hPa, corresponding to an elevation of -1000 m
to 2000 m
Storage/transport
1080 hPa to 660 hPa, corresponding to an elevation of -1000 m
to 3500 m
1)