7.6
Set values for monitoring the bearing temperature (optional)
Prior to commissioning
If the machine is equipped with bearing thermometers, set the temperature value for
disconnection on the monitoring equipment before the first machine run.
Table 7-2
Set values for monitoring the bearing temperatures before commissioning
Set value
Temperature
Alarm
115 °C
Shutting down
120 °C
Normal operation
Measure the normal operating temperature of the bearings T
op
at the installation location in
°C. Set the values for shutdown and warning corresponding to the operating temperature T
op
.
Table 7-3
Set values for monitoring the bearing temperatures
Set value
Temperature
Alarm
T
operation
+ 5 K ≤ 115 °C
Shutting down
T
operation
+ 10 K ≤ 120 °C
Commissioning
7.6 Set values for monitoring the bearing temperature (optional)
SIMOTICS M-1PH8 1PH818., 1PH822., 1PH828.
Operating Instructions 10/2017
93
Summary of Contents for SIMOTICS M-1PH818
Page 2: ...20 10 2017 15 09 V20 00 ...
Page 14: ...Introduction SIMOTICS M 1PH8 1PH818 1PH822 1PH828 14 Operating Instructions 10 2017 ...
Page 28: ...Description SIMOTICS M 1PH8 1PH818 1PH822 1PH828 28 Operating Instructions 10 2017 ...
Page 104: ...Operation 8 10 Faults SIMOTICS M 1PH8 1PH818 1PH822 1PH828 104 Operating Instructions 10 2017 ...
Page 166: ...Quality documents SIMOTICS M 1PH8 1PH818 1PH822 1PH828 166 Operating Instructions 10 2017 ...
Page 171: ...171 ...
Page 172: ...172 ...
Page 173: ...173 ...
Page 174: ...174 ...
Page 175: ...175 ...
Page 176: ...176 ...
Page 177: ...177 ...
Page 178: ...178 ...
Page 179: ...179 ...
Page 180: ...180 ...
Page 181: ...181 ...
Page 182: ...182 ...
Page 183: ...183 ...
Page 184: ...184 ...
Page 185: ...185 ...
Page 186: ...186 ...
Page 187: ...187 ...
Page 188: ...188 ...
Page 189: ...189 ...
Page 190: ...190 ...
Page 191: ...191 ...
Page 192: ...192 ...
Page 278: ...278 ...
Page 308: ...308 ...