Contents and chemical composition
Value
Iron
< 0.2 ppm
Ammonia
< 10 ppm
Dissolved solids
< 340 ppm
Conductivity
< 500 µS/cm
Mix additives in with the cooling water in appropriate quantities to protect against corrosion
and inhibit the growth of algae. The type and quantity of additive should be taken from the
respective manufacturer's specifications for these additives and the particular ambient
conditions.
Cooling unit
The use of a correspondingly dimensioned cooling unit ensures the coolant inlet temperature
of 25°C. You can operate several motors and/or the converter on one cooling unit.
Use a closed cooling cooling circuit. This will prevent deposits in the cooling circuit, cooling is
then permanently guaranteed.
The cooling unit is not part of the motor's scope of delivery.
ཱ
ི
ཱི
ུ
ཱུ
ྲྀ
ཷ
ླྀ
①
Filter
1
⑥
Coolant temperature sensing
②
Flow quantity display
①
⑦
Compressor/cooling unit
③
Flow regulating valve
①
⑧
Motor
④
Pump
⑨
Cooling unit
⑤
Cooling-medium reservoir
1
These components are not absolutely necessary.
Figure 4-1
Example of a cooling circuit
Preparations for use
4.4 Cooling water inlet temperature (water-cooled motor)
SIMOTICS HT Series HT-direct 1FW4...1......A
30
Operating Instructions 11/2018
Summary of Contents for SIMOTICS HT Series
Page 2: ...13 11 2018 16 25 V5 00 ...
Page 10: ...Table of contents SIMOTICS HT Series HT direct 1FW4 1 A 10 Operating Instructions 11 2018 ...
Page 26: ...Description SIMOTICS HT Series HT direct 1FW4 1 A 26 Operating Instructions 11 2018 ...
Page 118: ...Service and Support SIMOTICS HT Series HT direct 1FW4 1 A 118 Operating Instructions 11 2018 ...
Page 122: ...Quality documents SIMOTICS HT Series HT direct 1FW4 1 A 122 Operating Instructions 11 2018 ...
Page 127: ......