6.4.3
Connecting the grounding conductor
The grounding conductor cross-section of the motor must be in full conformance with the
installation specifications, e.g. in accordance with IEC 60034-1.
External conductor cross-section S
mm²
Grounding conductor cross-section
mm²
35
25
50
25
70
35
95
50
120
70
150
70
185
95
240
120
300
150
400
185
There is a hexagon bolt with a flat washer and a spring washer on the stator frame at the
designated connection point for the grounding conductor. The grounding conductor can be
connected as follows:
● With stranded cables with cable lugs
● With flat cables with cable end designed accordingly
As an alternative, you can connect the grounding conductor without cable lugs using a
clamping plate at the marked connection point.
Connecting the grounding conductor
● Use the connecting terminals designated for the grounding conductor in the terminal box.
● Ensure that the connecting surface is bare and is protected against corrosion using a
suitable substance, e.g. acid-free Vaseline.
● Arrange the flat washer and spring washer under the screw head.
Electrical connection
6.4 Preparation
SIMOTICS FD 1MQ1
Operating Instructions 01/2019
77
Summary of Contents for SIMOTICS FD 1MQ1
Page 2: ...28 01 2019 14 14 V11 01 ...
Page 144: ...Maintenance 9 2 Corrective Maintenance SIMOTICS FD 1MQ1 144 Operating Instructions 01 2019 ...
Page 170: ...Disposal 11 5 Disposal of components SIMOTICS FD 1MQ1 170 Operating Instructions 01 2019 ...
Page 172: ...Service and Support SIMOTICS FD 1MQ1 172 Operating Instructions 01 2019 ...
Page 176: ...Quality documents SIMOTICS FD 1MQ1 176 Operating Instructions 01 2019 ...
Page 181: ......