The connecting cables of the temperature sensors are routed to the main or auxiliary terminal
box, depending on the version. The connection and assignment of the terminals is specified in
the circuit diagram.
WARNING
Hazard due to electric shock
The installation of the temperature sensors for the winding monitoring with respect to the
winding is implemented according to the requirements for basic insulation. The temperature
sensor connections are located in terminal boxes, safe to touch, and have no protective
separation. This is the reason that in the case of a fault, a hazardous voltage can be present
at the measuring sensor cable. When touched, this can result in death, severe bodily injury
and material damage.
● When connecting the temperature sensor to external temperature monitoring devices,
when required, apply additional measures to fully comply with the requirements set out in
IEC 60664-1 or IEC 61800-5-1 "Hazard due to electric shock”.
6.6.6
Terminating the connection work (auxiliary circuit)
1. Before closing the auxiliary terminal box, please check that:
– The cables are connected in accordance with the terminal diagram.
– The cables are freely arranged so that they cannot come into contact with the machine,
and the cable insulation cannot be damaged.
– The inside of the terminal box is clean and free of any cable debris, dirt and foreign
bodies.
– The cable glands are firmly tightened, are suitable with respect to the degree of
protection, type of cable routing, permissible cable diameter, etc., and have been
mounted in full compliance with specifications and regulations
– The threads in the connection plate are sealed using cable and conductor entries, thread
adapters or sealing plugs that achieve the respective degree of protection.
– Unused cable entries are sealed. The sealing elements are firmly screwed in, and can
only be released using a tool.
– All of the seals/gaskets and sealing surfaces of the terminal box are in good condition
– The screws of all of the screw clamps are fully tightened, even if they are not being used.
2. Close the auxiliary terminal box using the cover supplied for this purpose. See section
"Tightening torques for screw and bolt connections (Page 169)" for the tightening torque of
the fixing bolts for the cover.
Electrical connection
6.6 Connecting the auxiliary circuits
SIMOTICS FD 1MM1
Operating Instructions 02/2019
93
Summary of Contents for SIMOTICS FD 1MM1 Series
Page 2: ...05 02 2019 16 03 V11 01 ...
Page 30: ...Description SIMOTICS FD 1MM1 30 Operating Instructions 02 2019 ...
Page 142: ...Maintenance 9 2 Corrective Maintenance SIMOTICS FD 1MM1 142 Operating Instructions 02 2019 ...
Page 166: ...Disposal 11 5 Disposal of components SIMOTICS FD 1MM1 166 Operating Instructions 02 2019 ...
Page 168: ...Service and Support SIMOTICS FD 1MM1 168 Operating Instructions 02 2019 ...
Page 172: ...Quality documents SIMOTICS FD 1MM1 172 Operating Instructions 02 2019 ...
Page 177: ......