6.5.12
Finishing connection work
1. Before closing the terminal box, please check that:
– The electrical connections in the terminal box have been made in accordance with the
specifications above and tightened with the correct tightening torque.
Remove the used bolts and fastening elements.
– The machine is connected in such a way that it rotates in the direction specified.
– The inside of the terminal box is clean and free of any cable debris, dirt and foreign
bodies.
– All of the seals and sealing surfaces of the terminal box are intact and in a good condition.
– Unused cable entries are closed and their plugs are tightly screwed in place, i.e. they can
only be released using a tool.
– The connecting cables are freely routed. The cable insulation cannot be damaged in
operation.
2. Close the terminal box using the cover fixing screws, see Chapter Tightening torques for
screw connections.
See also
Tightening torques for screw and bolt connections (Page 165)
Mounting/removing the terminal box (Page 82)
6.6
Connecting the auxiliary circuits
6.6.1
Selecting cables
Take the following criteria into account when selecting the connecting cables for the auxiliary
circuits:
● Rated current
● Rated voltage
● System-dependent conditions, such as ambient temperature, routing type, cable cross-
section as defined by required length of cable, etc.
● Requirements according to IEC/EN 60204‑1
Electrical connection
6.6 Connecting the auxiliary circuits
SIMOTICS FD 1LH1
94
Operating Instructions 01/2019
Summary of Contents for SIMOTICS FD 1LH1
Page 2: ...23 01 2019 19 26 V11 01 ...
Page 28: ...Description SIMOTICS FD 1LH1 28 Operating Instructions 01 2019 ...
Page 122: ...Operation 8 10 faults SIMOTICS FD 1LH1 122 Operating Instructions 01 2019 ...
Page 140: ...Maintenance 9 2 Corrective Maintenance SIMOTICS FD 1LH1 140 Operating Instructions 01 2019 ...
Page 162: ...Disposal 11 5 Disposal of components SIMOTICS FD 1LH1 162 Operating Instructions 01 2019 ...
Page 164: ...Service and Support SIMOTICS FD 1LH1 164 Operating Instructions 01 2019 ...
Page 168: ...Quality documents SIMOTICS FD 1LH1 168 Operating Instructions 01 2019 ...
Page 173: ......