Commissioning
7.5 Switching on
1FU8
68
Operating Instructions, 02/2016, 5 610 70000 02 000
7.5
Switching on
Measures for start-up
After installation or inspections, the following measures are recommended for normal start-
up of the machines:
●
Start the machine without a load. To do this, close the circuit breaker and do not switch
the machine off prematurely. Switching the machine off again while it is starting up and
still running at slow speed should be kept to a bare minimum, for example for checking
the direction of rotation or for checking in general. Allow the machine to run to a standstill
before switching it back on again.
●
Check mechanical operation for noise or vibration at the bearings or end shields.
●
If the machine is not running smoothly or is emitting abnormal noises, switch it off, and
determine the cause of the fault as it runs down.
●
If mechanical operation improves immediately after the machine is switched off, then the
cause is magnetic or electrical, e.g. voltage imbalance, magnetic imbalance. If
mechanical operation does not improve immediately after switching the machine off, then
the cause is mechanical, e.g. an imbalance in the electrical machines or in the driven
machine, inadequate alignment of the machine set, operation of the machine with the
system resonating (system = m base frame + foundations etc.).
●
If the machine runs perfectly in terms of its mechanical operation, switch on any cooling
devices present and continue to monitor the machine for a while as it idles.
●
If it runs perfectly, connect a load. Check that it runs smoothly.
Read off and document the values for voltage, current, and power.
Where possible, read off corresponding values for the driven machine and document
them as well.
●
Monitor the bearing temperature, winding temperature, etc. until the system reaches a
steady state.
Document these, provided this is possible with existing measuring instruments.
●
In order to guarantee reliable starting and/or sufficient margin to the stall torque, in the
lower frequency range a voltage boost of approx. 10 … 20 % of the 50 Hz rated voltage
may be required. If necessary, contact the manufacturing plant.
●
The coast down time of the machine can be significantly reduced by short-circuiting the
terminals (also through resistors). Braking by short-circuiting the stator winding does not
have any negative effect on the magnets of permanent-magnet synchronous machines.
Summary of Contents for SIMOTICS A 1FU8
Page 1: ......
Page 2: ......
Page 10: ...Inhaltsverzeichnis 1FU8 10 Betriebsanleitung 02 2016 5 610 70000 02 000 ...
Page 12: ...Einleitung 1 1 Über diese Anleitung 1FU8 12 Betriebsanleitung 02 2016 5 610 70000 02 000 ...
Page 30: ...Beschreibung 3 3 Aufbau 1FU8 30 Betriebsanleitung 02 2016 5 610 70000 02 000 ...
Page 80: ...Betrieb 8 4 Ausschalten 1FU8 80 Betriebsanleitung 02 2016 5 610 70000 02 000 ...
Page 106: ......
Page 108: ...Service Support A 3 Weitere Dokumente 1FU8 108 Betriebsanleitung 02 2016 5 610 70000 02 000 ...
Page 112: ......
Page 115: ......
Page 116: ......
Page 124: ...Table of contents 1FU8 10 Operating Instructions 02 2016 5 610 70000 02 000 ...
Page 142: ...Description 3 3 Installation 1FU8 28 Operating Instructions 02 2016 5 610 70000 02 000 ...
Page 225: ......
Page 226: ......